4-10 Configuring SLC 5/03, 5/04, and 5/05 Processors

Configuring a
Standard-Mode DF1
Half-Duplex Master Station

Choose standard mode if you want to query slave stations for
information based upon user-configured polling ranges. This mode is
used most often in general point-to-multipoint configurations.

To configure the processor for a master station using standard
communication, place the processor into program mode and follow
the steps below using your programming software:

1. To bring up the Channel

Configuration interface,
double-click on the Channel
Configuration icon.

2. Define the location of the

diagnostic file used for
Channel Status here. For
Channel Status details, see
page 4-16.