7-24 Configuring Logix Controllers

DF1 Point-to-Point
Diagnostic Counters

DF1 Point-to-Point driver status data is stored in the Diagnostic
Counter attribute of the DF1 communication object. You must define a
controller tag to be the destination for this data and copy the system
data to this tag using a GSV instruction. For the required ladder logic,
see page 7-25.

1. To bring up the Controller Tag

interface, click on the Controller Tags
icon.

2. For details of the

DisgnosticCounter
files, see Table 7.9.

Table 7.9 DF1 Full-Duplex (Point-to-Point) Diagnostic Counters

Status Field

Diagnostic Tag Array
Location

Definition

signature (67

10

)

word 0

DF1 Point-to-Point is the configured protocol

DTR (Data Terminal Ready)

word 1;bit 4

The status of the DTR handshaking line (asserted by the controller)

DCD (Data Carrier Detect)

word 1;bit 3

The status of the DCD handshaking line (received by the controller)

DSR (Data Set Ready)

word 1;bit 2

The status of the DSR handshaking line (received by the controller)

RTS (Request to Send)

word 1;bit 1

The status of the RTS handshaking line (asserted by the controller)

CTS (Clear to Send)

word 1;bit 0

The status of the CTS handshaking line (received by the controller)

packets sent

word 2

The total number of DF1 packets sent by the controller (including
message retries)

packets received

word 3

The number of packets received with no errors

undelivered packets

word 4

The number of packets that were sent by the controller but not
acknowledged by the destination device

unused

word 5