Publication AG-UM008C-EN-P - February 2005

6-14 Configuring MicroLogix 1000 Controllers

Table 6.2 DF1 Full-Duplex Configuration Parameters MicroLogix 1000

Messaging

Messaging in a MicroLogix 1000 controller can occur between:

a master station and a slave station. For more information see
the chapter pertaining to the master device you are using.

a slave station and its master station. See Polled
Report-by-Exception.

between two controllers connected via a point-to-point link.

Parameter

Options

Default

Baud Rate

Toggles between the communication rates of 300, 600, 1200, 2400,
4800

(1)

, 9600, 19200, and 38400

(1)

.

9600

(2)

Node Address

Valid range is 0 to 254 decimal for MicroLogix 1000 Series C and later
discrete and all MicroLogix 1000 analog. Not configurable for
MicroLogix 1000 Series A and B discrete.

1

Parity

None

No Parity

Stop Bits

None

1

Error Detection

None

CRC

DLE NAK
Retries

None

N retries

(3)

DLE ENQ Retries

None

N retries

(3)

ACK Timeout

None

1 second

Duplicate
Packet
Detection

None

Enabled

Control Line

None

No
Handshaking

Embedded
Responses

None

Enabled

(1) Applicable only to MicroLogix 1000 Series D or later discrete and all MicroLogix 1000 analog controllers.

(2) If retentive communication data is lost, the default is 1200 for MicroLogix 1000 Series A, B, or C discrete only.

For MicroLogix 1000 Series D or later discrete and all MicroLogix 1000 analog, if retentive communication data is lost, baud rate defaults to
9600.

(3) N=255 for MicroLogix 1000 Series A and B discrete.

N=6 for MicroLogix 1000 Series C and later discrete and all MicroLogix 1000 analog.