Appendix

B

Basic DF1 Protocol Troubleshooting

Appendix Objectives

This appendix helps you troubleshoot communication problems.

General Tips

When you encounter problems, check these items:

cabling (cable length, connectors, pinouts, etc.)

power connections

communication rate settings for all devices must match

control line configuration

handshaking parameters

error detection selection for all devices must match

(BCC or CRC)

Communication
Troubleshooting

For new installations, if possible, setup the communications in the lab
before installing the processors in the field using a directly connected
null-modem cable. Verify that the protocol settings and addressing are
properly configured for all processors. For multi-drop configurations,
you need only verify Master-to-Slave communications. Next, replace
the null-modem cable with modem cables and introduce the modems
as the link between the devices. Troubleshoot the modem link(s).

For information about

See page

general tips

B-1

communication troubleshooting

B-1

DF1 half-duplex protocol

B-4

DF1 full-duplex protocol

B-6

DF1 radio modem protocol

B-7