Configuring a slave station, Configuring a slave station -10 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 214

Advertising
background image

Publication AG-UM008C-EN-P - February 2005

6-10 Configuring MicroLogix 1000 Controllers

Configuring a Slave Station

To choose the controller as a slave station, follow the steps below
your programming software:

IMPORTANT

The MicroLogix 1000 controller must be online to be
configured. When offline, the controller does not
allow key parameters to be available to set.

1. Check that you are online with the controller

to be configured. You should see Remote Run or
Remote Program.

2. Double-click on the Channel Configuration icon

to bring up the Channel Configuration interface.

3. Scroll down the list and

choose the desired baud rate.

4. Click the radio button and

choose Half-Duplex Slave.

5. Configure the communication

driver characteristics
according to Table 6.1.