Installing the controller, Installing the controller -3 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual
Page 207
Publication AG-UM008C-EN-P - February 2005
Configuring MicroLogix 1000 Controllers 6-3
Installing the Controller
For details about installing the controller see the MicroLogix 1000
Programmable Controllers User Manual, publication number
1761-UM003. Cable designations are shown in each example
configuration as well as in Appendix A.
Figure 6.2 MicroLogix Cable Pinouts
8-pin Mini Din
9-pin D-shell
5
4
3
2
1
9
8
7
6
1 2
3
4
5
6 7 8
1761-CBL-PM02 Series B Cable
MicroLogix Optical
Isolator
Modem
8-pin Mini DIN
9-pin Female
9-pin Male
9-pin
or 25-pin
5 DCD
DCD
1
1
1
8
4 RXD
RXD
2
2
2
3
7 TXD
TXD
3
3
3
2
2 GND
DTR
4
5
5
7
GND
5
4
4
20
DSR
6
6
6
6
3 RTS
RTS
7
7
7
4
6 CTS
CTS
8
8
8
5
A-B cable
Standard A-B cables:
•
1761-CBL-PM02 Series B or
Higher (6.5 feet)
•
1761-CBL-AP00 (17.7 inches)
User-supplied modem
cable
User supplied cable
Optical Isolator