7-38 Configuring Logix Controllers

Logix Controller Error
Codes for PLC and SLC
Messages

With the release Logix R10.x firmware, you will find new error code
values for errors that are associated with PLC and SLC message types
(PCCC messages).

This change lets RSLogix 5000 software display a more
meaningful description for many of the errors. Previously the
software did not give a description for any of the errors
associated with the 00F0 error code.

The change also makes the error codes more consistent with
errors returned by other controllers, such as PLC-5 controllers.

The following table shows the change in the error code values from
R9.x and earlier to R10.x and later. As a result of the change, the .ERR
member returns a unique value for each PCCC error. The .EXERR is no
longer required for these errors.

R9.x and earlier

R10.x and later

Description

.ERR

.EXERR

.ERR

.EXERR

0010

1000

Illegal command or format from local processor

0020

2000

Communication module not working

0030

3000

Remote node is missing, disconnected, or shut down

0040

4000

Processor connected but faulted (hardware)

0050

5000

Wrong station number

0060

6000

Requested function is not available

0070

7000

Processor is in Program mode

0080

8000

Processor’s compatibility file does not exist

0090

9000

Remote node cannot buffer command

00B0

B000

Processor is downloading so it is not accessible

00F0

0001

F001

Processor incorrectly converted the address

00F0

0002

F002

Incomplete address

00F0

0003

F003

Incorrect address

00F0

0004

F004

Illegal address format - symbol not found

00F0

0005

F005

Illegal address format - symbol has 0 or greater than the maximum number of
characters supported by the device

00F0

0006

F006

Address file does not exist in target processor

00F0

0007

F007

Destination file is too small for the number of words requested

00F0

0008

F008

Cannot complete request
Situation changed during multipacket operation

00F0

0009

F009

Data or file is too large
Memory unavailable

00F0

000A

F00A

Target processor cannot put requested information in packets

00F0

000B

F00B

Privilege error; access denied