Configuring the processor, Configuring the processor -3 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 189

Advertising
background image

Publication AG-UM008C-EN-P - February 2005

Configuring SLC 500 Processors with 1747-KE Interface Modules 5-3

For details about installing the interface module, see the DH-485/

RS-232C Interface Module User Manual, publication 1747-6.12.

Figure 5.2 1747-KE Serial Port Pin Assignments

Configuring the Processor

As you are specifying each module within the chassis scanned by the

SLC 500 processor, remember to specify a slot for the 1747-KE
module. Configure the DH-485 node address of the programming
terminal as 0-31; the default is 0.

Also, define a node address for the SLC 500 processor. This address,
when combined with the group number (configured on the interface
module when in remote mode), comprises the remote station’s
address.

Series A interface modules may only be configured using an ASCII
terminal, while series B interface modules may be either configured
using an ASCII terminal or using ladder logic in the SLC 500
communicating across the backplane.

9-pin female connector

To modem

Connect to a 1747-AIC using 1747-C11 or 1747-C13

DH-485/RS-232C

ACT

485

CFG

DF1

Fault

BA LOW

H/D

F/D

3

4

5

6

1

2

3

4

JW4 Configuration
Mode Setting

JW4 Run Mode Setting

or connect to the SLC 500 processor using 1747-C13

JW1 CONFIG port is
configured for RS-232.

JW2 DF1 port is
configured for RS-232.

Set to RUN after module
is configured.

9-pin female

25-pin

9-pin

RXD.IN

2

3

2

TXD.OUT

3

2

3

DTR.OUT

4

20

4

SIG.GND

5

7

5

DSR.IN 6

8

1

RTS.OUT

7

4

7

CTS.IN

8

5

8