Configuring the 1747-ke interface module, Configuring the 1747-ke, Interface module -4 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 190: Prepare to configure the driver -4, Prepare to configure the driver

Advertising
background image

Publication AG-UM008C-EN-P - February 2005

5-4 Configuring SLC 500 Processors with 1747-KE Interface Modules

Configuring the 1747-KE

Interface Module

To configure the interface module with an ASCII terminal:

prepare to configure the driver

configure the DF1 protocol driver, and

save the configuration

Prepare to Configure the Driver

1. Connect an ASCII terminal or personal computer running

terminal emulation software to the interface module’s CONFIG
port.

2. Turn on power to the chassis containing the interface module.

3. Run the ASCII terminal emulation software, and configure the

software to match the default CONFIG port parameters, which
are the following:

4. Configure the DF1 port as shown in Figure 5.3.

DH-485/RS-232C

ACT

485

CFG
DF1

Fault

BA LOW

H/D

F/D

41200

ASCII

9-pin female 9-pin female

2

2

3

3

5

5

Parameter

Selections

Baud rate

1200

Bits per character

8

Parity

none

Stop bits

one