Publication AG-UM008C-EN-P - February 2005

Chapter

5

Configuring SLC 500 Processors with 1747-KE
Interface Modules

Chapter Objectives

This chapter helps you set up an SLC 500 fixed or modular processor
(SLC 5/01 or 5/02 processor) with a 1747-KE as a remote station or as
a station on a point-to-point link.

Overview

To configure an SLC 500 processor with a 1747-KE interface module
as a remote station:

1. Install the processor (modular processors only).

2. Install the 1747-KE module.

3. Configure the processor using your programming software.

4. Define the 1747-KE communication characteristics using an

ASCII terminal or terminal emulation software like
Hyperterminal in Windows 95. Connect a properly wired cable
to the interface module’s serial port (DF1 port).

5. Install and configure the modem for communication with the

1747-KE module; connect the modem to the 1747-KE module’s
serial channel. See Chapter 8.

For information about:

See page:

an overview of the tasks required to configure an SLC 500 processor
with a 1747-KE module as a remote station

5-1

installing the SLC 500 processor

5-2

installing the 1747-KE interface module

5-2

configuring the SLC 500 processor

5-3

configuring the 1747-KE interface module

5-4

configuring messages in the SLC 5/02 processor

5-11