Testing Air Temperature Sensors

1. Press the Test button. The Test menu displays.

2. Press the  or  button to highlight the Test Temp. Sensor option, and then press the OK

button. The Test Temp. Sensor screen displays.

3. Press the  or  button to select the air temperature sensor number that you want to test.

4. Press the OK button to test the air

temperature sensor.

This test returns the status of the device, the

device serial number, the air temperature,

the two-wire voltage drop, and the version of

the device. If any zones or programs are

running when the test is activated, watering

will pause for 10 minutes.

5. Repeat steps 3 and 4 until you have tested all the air temperature sensors that you wish to

test.

6. When you have finished viewing the test results, press the RUN button to return to the Run

menu.

Testing the Two-Wire

1. Press the Test button. The Test menu displays.

2. Press the  or  button to highlight the Test Two-Wire option, and then press the OK

button. The Test Two-Wire screen indicates

that the test is in progress.

The test results display on the screen.