3.2.15 Analog Output Menu

The ALGOUT menu is used only if the analog output option is installed. If the analog output option is installed,

configure all other indicator functions and calibrate the indicator before configuring the analog output. See

Section 10.11 on page 108 for analog output calibration procedures.

SETUP

....

....

....

ALGOUT

....

number

TWSPAN

OFF

ON

MAXNEG

MINNEG

OFF

ON

ERRACT

FULLSC

ZEROSC

HOLD

OUTPUT

0-10V

0-20MA

4-20MA

MODE

GROSS

NET

MAX

10000

number

TWZERO

number

MIN

number

0

Figure 3-23. Analog Output Menu

Table 3-17. Analog Output Menu Parameters

ALG OUT Menu

Parameter

Choices

Description

Level 2 submenus

MODE

GROSS
NET

Defines if the output follows the GROSS or NET weight.

OUTPUT

0-10V
0-20MA
4-20MA

Selects whether the analog output supplies voltage (0–10 V), current (0-20mA),

or current (4-20mA).

ERRACT

FULLSC
HOLD
ZEROSC

Error action. Specifies how the analog output responds to system error conditions.
Possible values are:

FULLSC: Set to full value (10 V or 20 mA, depending on output setting)
HOLD: Hold current value
ZEROSC: Set to zero value (0 V or 4 mA, depending on output setting)

MIN

0.000000
number

Specifies the minimum weight value tracked by the analog output. Specify a value in the range
0–999999.

MIN NEG

OFF
ON

Set to ON if the MIN value is negative.

MAX

10000.00
number

Specifies the maximum weight value tracked by the analog output. Specify a value in the range
0–999999.

MAX NEG

OFF
ON

Set to ON if the MAX value is negative.

TWZERO

000000
number

Calibrate zero. Adjust the analog output zero calibration. See Section 10.11 on page 108.

TWSPAN

000000
number

Calibrate span. Adjust the analog output span calibration. See Section 10.11 on page 108