0 setpoints, 1 batch and continuous setpoints, Setpoints – Rice Lake 880 Performance Series Indicator/Controller Technical/Service Manual User Manual

Page 87

Advertising
background image

Setpoints

81

8.0

Setpoints

The

880

indicator provides 20 configurable setpoints for control of both indicator and external equipment

functions. Setpoints can be configured to perform actions or functions based on specified parameter conditions.

Parameters associated with various setpoint kinds can, for example, be configured to perform functions (print, tare,

accumulate), to change the state of a digital output to control external equipment functions, or to make conditional

decisions.

Note

See Section 3.2.13 on page 49 for setpoint menu layout.

Weight-based setpoints are tripped by values specified in primary units only.

8.1

Batch and Continuous Setpoints

880

setpoints can be either continuous or batch setpoints.

Continuous setpoints

are free-running: the indicator constantly monitors the condition of free-running setpoints at

each A/D update. The specified setpoint action or function is performed when the designated setpoint

parameter conditions are met. A digital output or function assigned to a free-running setpoint continuously

changes state, becoming active or inactive, as defined by the setpoint parameters.

Batch setpoints

are active one at a time, in an ordered sequence. The

880

can use setpoints to control up to 20

separate batch processing steps.
A digital output associated with a batch setpoint is active until the setpoint condition is met, then latched for

the remainder of the batch sequence.
To use batch setpoints, the BATCHG parameter on the SETPTS menu must be set to auto or manual. AUTO

sequences repeat continuously after receiving a single initial BATSTR signal. MANUAL sequences require a

BATSTR signal each time a single batch is run. The BATSTR signal can be initiated by a digital input, serial

command. Set the BATCHG parameter to OFF to disable batch setpoints.
For setpoint kinds that can be used as either continuous or batch setpoints, the BATSEQ parameter must also

be set ON. (Setpoint kinds that can only be used as batch setpoints do not require the BATSEQ parameter.) If

the setpoint is defined but the BATSEQ parameter is off, the setpoint operates as a continuous setpoint, even

during batch sequences.

Note

In applications that contain both batch setpoint routines and continuous setpoints, continuous setpoints
should be kept separate from the batch sequence. This is especially true when using CONCUR or TIMER
setpoints to perform actions or functions based on the batch sequence. CONCUR and TIMER setpoints should
not be included in the referenced START and END setpoint sequence.

Kind

Description

Batch

Continuous

OFF

Setpoint turned off/ignored.

GROSS

Gross setpoint. Performs functions based on the gross weight. The target
weight entered is considered a positive gross weight.

X

X

NET

Net setpoint. Performs functions based on the net weight. The target weight
entered is considered a positive net weight value.

X

X

–GROSS

Negative gross weight. Performs functions based on the gross weight. The
target weight entered is considered a negative gross weight.

X

X

–NET

Negative net weight. Performs functions based on the net weight. The target
weight entered is considered a negative net weight value.

X

X

%REL

Percent relative setpoint. Performs functions based on a specified percentage
of the target value of a referenced setpoint, using the same weight mode as the
referenced setpoint. The actual target value of the %REL setpoint is calculated
as a percentage of the target value of the referenced setpoint.

X

X

PAUSE

Pauses the batch sequence indefinitely. A BATSTR signal must be initiated to
continue the batch process.

X

DELAY

Delays the batch sequence for a specified time. The length of the delay (in
tenths of a second) is specified by the VALUE parameter.

X

Table 8-1. Setpoint Kinds

Advertising