System Management Interface Based on HPI-B (Centellis 2000 R3.0/4411) User’s Guide (6806800P20C)

82

4.6.2

External Cooling Management

If you decide not to rely on the ATCA-MF106/SAM1411 cooling management, you can switch
the ATCA-MF106/SAM1411 cooling management off. Then you have the following two
options to control the fan speed and thus perform cooling management:

Use a Linux example program

Access HPI controls

4.6.2.1

Toggling Between External and Internal Cooling Management

Although we strongly recommend to rely on the ATCA-MF106/SAM1411 shelf management
software for cooling management, in some situations you may want to control the fan speed
manually or you may want to use external shelf management software. For this purpose, the
internal cooling management can be switched off.

If the internal cooling management is switched off, the ATCA-MF106/SAM1411 cooling
management software still monitors temperature sensors and handles all events, but no set
operations are actually executed. If the internal cooling management is switched on again, the
cooling management software executes all necessary cooling actions according to the current
state of the system.

In order to switch on/off the internal cooling management, use the Linux example program
hpicooling

which is delivered with the ATCA-MF106/SAM1411 software. The usage of the

example program is as follows.

Description

This service allows you to switch on/off the internal cooling management.

Damage of Shelf and Blades/FRUs
The cooling management as performed by the ATCA-MF106/SAM1411 provides optimized
cooling for the shelf and all blades/FRUs in it. It has been adapted and optimized for the shelf.
Performing cooling management manually or via (inadequate) external shelf management
software may lead to overheating and thus damage of the shelf and blades/FRUs in it.
Perform cooling management only via the ATCA-MF106/SAM1411 software.