12 Input Digital Option Card -

Digital Inputs

12 Input Option Card -

Output Relays

Recommended wiring - RLE Technologies recommends 18 to 20AWG stranded copper for connection from

each monitored point to a terminal block (TB) connection on the Falcon. RLE recommends no more than 500
feet at this specification. If longer runs are needed, please contact RLE Technologies for application guidance.
Shielded twisted pair is recommended for analog signal transmitters being wired outside of conduit runs and
dropped ceiling applications.

+ -

Ch15

+ -

Ch16

+ -

Ch17

+ -

Ch18

+ -

Ch20

+ -

Ch19

+

-

Ch14

+

-

Ch13

+

-

Ch12

+

-

Ch11

+

-

Ch10

+

-

Ch09

TB7

TB8

24 Input Digital Option Card - Digital Inputs

+ -

Ch27

+ -

Ch28

+ -

Ch29

+ -

Ch30

+ -

Ch32

+ -

Ch31

+

-

Ch26

+

-

Ch25

+

-

Ch24

+

-

Ch23

+

-

Ch22

+

-

Ch21

TB9

TB10