Falcon user guide – RLE FMS8 User Manual

Page 58

Advertising
background image

Falcon User Guide

58

Per channel, select the appropriate number to modify
inputs and either pick an item from a menu or type
the value or description for the item selected. If an
option card is present, the system will automatically
recognize the number of points to configure.

Analog Points
Gain for 4-20mA Transducer

(Sensor High Range – Sensor Low Range)/4

Offset for 4-20mA Transducer

Sensor Low Range – Gain

Digital Points
The table represents control values for the output
relays (K1 and K2) and optional relays (K3, K4, K5
and K6). Select the appropriate value of the relay
to activate it, or add the respective values of the
appropriate alarm condition to activate more than
one output relay. Each input can have individual
control values.

Examples:
Relay Control: 2 - Activates relay K2 for either an

analog 2nd Stage High Alarm or a dry contact
change-of-state.

Relay Control: 64 - Activates relay K3 for an analog

2nd Stage Low Alarm.

Relay Control: 35 - Activates relays K1, K2, and K4

for either an analog 2nd Stage High Alarm or
a dry contact change-of-state (1+2+32).

Relay Control: 10 - Activates relay K2 for either

an analog 2nd Stage High or 2nd Stage Low
Alarm (8+2).

K1 Digital Alarm 1

Relay Alarm Condition Value
K1 High2 Analog Alarm 1
K1 Low2 Analog Alarm 4

K2 High2 Analog Alarm 2
K2 Low2 Analog Alarm 8
K2 Digital Alarm 2
K3 High2 Analog Alarm 16
K3 Low2 Analog Alarm 64
K3 Digital Alarm 16
K4 High2 Analog Alarm 32
K4 Low2 Analog Alarm 128
K4 Digital Alarm 32
K5 High2 Analog Alarm 256
K5 Low2 Analog Alarm 1024
K5 Digital Alarm 256
K6 High2 Analog Alarm 512
K6 Low2 Analog Alarm 2048
K6 Digital Alarm 512

Press Enter (

↵) to advance to next channel

or ESC to abort and back up one menu

level.

** System Menu/Help **

SS - System Status

CA - Current Alarms

KA - Kill All Alarms

LM - Log Menu

TI - Display Date/Time

AD - ADC Input Values

MS - Modem Stats

NS - Network Stats

AT - Arp Table

SC - System Confi g

DU - Dump Network Packets

NT - Network Trace

PING - Ping an IP Address

EX - Exit to Bootloader

Enter Menu Selection >

Enter Menu Selection > SC ******

** Main Confi guration Menu **

1. System Menu

2. IP Confi g Menu

3. Modem Confi g menu

4. EIA-485 Confi g menu

5. Factory Menu

6. Load/Save Confi g Data

7. Confi guration Password

8. E-Mail, SMTP Confi g Menu

X. Exit

Enter Menu Selection >

Enter Menu Selection >1

System Confi guration Menu

1. System Name: Falcon Monitoring System

2. Clock: 10/27/00 16:37:17

3. Keypad Access

4. Inputs

5. Relays

6. Battery

7. Analog Averaging: 0

8. Persistent Traps: 0

9. Slave Inputs

10. Slave Relays

11. Schedules

12. BACnet

13. Exit & Save

Enter Menu Selection >

Enter Menu Selection >4

Master Unit: RLE CR Wall Unit

Input Confi guration Menu

Channel #A1 of 32

Current Readings: Raw = 11.652 mA

Calc = 46

1. Type: 4-20

2. Gain: 35

3. Offset: -55

4. High Limit 2: 85

5. High Limit 1: 80

6. Low Limit 1: 60

7. Low Limit 2: 50

8. Relay Cntrl: 0

9. Unit of Measure: ºF

10. Label: Room Temperature

11. Alarm Delay: 0 (Secs)

12. Hysteresis: 0

13. Alarm Dial Out: 1,0,0,0,0

14. BACnet Instance: 0

15. BACnet Units: 0

18. Email Recipients:

19. Alarm Disable Sch: None

20. Previous Channel

21. Next Channel

22. Return

Enter Menu Selection >

Enter Menu Selection >1

Modify Input Type

1. Not Installed

2. Analog 4-20

3. Digital NO

4. Digital NC

5. Digital Status

Enter new type >