Falcon User Guide

30

Falcon Links
The Falcon Links link allows up to four
Falcons or IP addressable devices to link to the
Falcon.

Modem
The Modem link allows users to configure the
Falcon’s internal modem. The initialization string
can be a maximum of 38 characters.

&c1

and

&d3

are mandatory.

s0=1

sets the modem to answer

after one ring.

The dial prefix should be a specific Hayes
compatible command or dial modifier. It is also
limited to 38 characters. The default is set to

atdt

.

Pager Deliveries

designates the number

of times to call the pager until the alarm is
acknowledged - 1 to 255. Pagers are called in
sequence. For example, if

Pager Deliveries

is

set to 3 and pagers 1, 7, and 10 are programmed to
be notified, the Falcon dials 1, 7, 10, 1, 7, 10, 1,
7, 10. As soon as the alarm is acknowledged, the
Falcon quits dialing the pagers with that particular
access code. Pagers with different access codes are
still dialed.

Pager Interval

allots the number of minutes to

wait between redials.

Pager No Ack Alarm

establishes a number to

call if the alarm isn’t acknowledged. A numbered
contact (one through 16) designates the number to
call.

Pager Baud Rate

designates the pager baud rate.

Pager Unsuccessful Traps

will allow the

Falcon to send an SNMP trap to the NMS if set to

YES

.

Pager Resend

will send all unacknowledged

alarms in the Alarm History menu if set to

YES.

It will only send the last unacknowledged alarm if
set at

NO.

Modem Password

defines a remote access

password, seven characters max.

Redial Attempts

sets a number of times to call a

number until the call is successful, from one to 255.

Redial Interval

establishes the number of

minutes to wait between redials, from one to 255.

Comm Check Phone

defines a numbered contact

(one through 16) to call to check communications.

Comm Check Time

sets a time (24 hour format) to

make the communications check.

Force Alarm Acknowledge Code

acknowledges

all unacknowledged alarms. This acts as a master
code and can override all other alarm acknowledge
codes.

Changes will not go into effect until the

Submit

Changes

button is clicked.