Falcon user guide, Designates the pager baud rate – RLE FMS8 User Manual

Page 69

Advertising
background image

Falcon User Guide

69

Other settings available from the Modem
Configuration Menu:

Option

pd

designates the number of times to call the

pager until the alarm is acknowledged - 1 to 255.
Pagers are called in sequence. For example, if

pd

is set to 3 and pagers 1, 7, and 10 are programmed
to be notified, the Falcon dials 1, 7, 10, 1, 7, 10, 1,
7, 10. As soon as the alarm is acknowledged, the
Falcon quits dialing the pagers with that particular
access code. Pagers with different access codes are
still dialed.

p

i allots the number of minutes to wait between

redials.

pa

establishes a number to call if the alarm isn’t

acknowledged (

pi

time - 1). A numbered contact

(one through 16) designates the number to call.

pb

designates the pager baud rate.

Pager Unsuccessful Traps

will allow the

Falcon to send an SNMP trap to the NMS if set to

YES

.

Pager Resend

will send all unacknowledged

alarms in the Alarm History menu if set to

YES.

It will only send the last unacknowledged alarm if
set at

NO.

pw

defines a remote access password, seven

characters max.

r

sets a number of times to call a number until the

call is successful, from one to 255.

v

establishes the number of minutes to wait between

redials, from one to 255.

h

defines a numbered contact (one through 16) to

call to check communications.

t

sets a time (24 hour format) to make the

communications check.

** System Menu/Help **

SS - System Status

CA - Current Alarms

KA - Kill All Alarms

LM - Log Menu

TI - Display Date/Time

AD - ADC Input Values

MS - Modem Stats

NS - Network Stats

AT - Arp Table

SC - System Confi g

DU - Dump Network Packets

NT - Network Trace

PING - Ping an IP Address

EX - Exit to Bootloader

Enter Menu Selection >

Enter Menu Selection > SC ******

** Main Confi guration Menu **

1. System Menu

2. IP Confi g Menu

3. Modem Confi g menu

4. EIA-485 Confi g menu

5. Factory Menu

6. Load/Save Confi g Data

7. Confi guration Password

8. E-Mail, SMTP Confi g Menu

X. Exit

Enter Menu Selection >

Enter Menu Selection >3

** Modem Confi g Menu **

-i Enter new initialization string:

at&d3&c1s0=1

-f Enter new dial prefi x: atdt

-pn Phone numbers

-pd Enter new pager deliveries: 1

-pi Enter new pager interval: 5

(Minutes)

-pa Enter Pager No Ack Alarm: 0

-pb Enter Pager Baud Rate: 1200

-pu Pager Unsuccessful Traps: No

-pr Pager Resend Enabled: No

-pw Enter new modem password: rletech

-r Enter new redial attempts: 10

-v Enter new redial interval: 1

(Minutes)

-h Enter new comm check phone: 0

-t Enter new comm check time:

-a Force alarm ack code:

-q quit

-x Exit & Save (Warning: This will dis-

connect & initialize the modem)

Enter Menu Selection >

Enter Menu Selection >pd

Enter new pager deliveries: 5

Enter Menu Selection >pi

Enter new pager interval: 10

Enter Menu Selection >pa

Enter Pager No Ack Alarm: 6

Enter Menu Selection >pb

Enter Pager Baud Rate: 2400

Enter Menu Selection >pw

Enter new modem password: pass4

Enter Menu Selection >r

Enter new redial attempts: 4

Enter Menu Selection >v

Enter new redial interval: 3

Enter Menu Selection >h

Enter new comm check phone: 0

Enter Menu Selection >t

Enter new com check time:(HH:MM):01:00

Enter Menu Selection >a

Force alarm ack code:

Enter Menu Selection >pu

Pager Unsuccessful traps: Yes/No

Enter Menu Selection >pr

Pager Resend Enabled: Yes/No

a

acknowledges all unacknowledged alarms. This

acts as a master code and can override all other
alarm acknowledge codes.