Appendix b technical specifications – RLE FMS8 User Manual

Page 89

Advertising
background image

Falcon User Guide

89

Appendix B
Technical Specifications

Dimensions 16.8”W x 1.8”H x 7.9”D
(427mmW x 46mmH x 201mmD)
Weight 6lbs. (2.72kg)
Operating Environment 32°F to 158°F (0°C to 70°C)
5% to 95% RH, non-condensing
10,000’ (3048m) max.
Storage Temperature -4°F to 185°F (-20°C to 85°C)
Power

24VDC model: 24VDC ± 10%, 800mA max.

48VDC model: 36VDC to 72VDC, 500mA max.

Keypad Interface 3000VAC rms optically installed
Universal Inputs Eight Inputs
Analog: 4-20mA - 12 Bit A/D conversion
Digital: Dry contact
Transient Suppression - 600W peak pulse power dissipation on 10/1000uS

waveform

Overvoltage tolerant to ± 16.5V
Fused input: 300mA resettable fuse
Optional Digital Inputs 3000VAC rms optically isolated
Digital Outputs 2 - dry contact form “C”
Contact rating: 1 Amp @ 24VDC/0.5A @ 120VAC, resistive
Internal Modem FCC part 68 approved
Isolation: 1500VAC rms isolation barrier
Baud rate: 33.6Kbps standard
2100V peak surge protection
Communications EIA-232 port: 3000VAC rms optically isolated, 15kV ESD protection
EIA-485 port: 3000VAC rms optically isolated, transient suppression -

600W peak pulse power, dissipation on 10/1000uS waveform

Ethernet 10BaseT port: SNMP V1 support, UDP command set,

1500VAC rms isolation

Internal Hardware 16 Bit 68HC16Z1 Microprocessor
64K ROM; 256K/512K Flash Memory
128K RAM; 32/128K NVRAM
Real-time clock
Option Cards EXP12: 12 digital inputs, 4 relay (digital) outputs

EXP12-U: 12 universal inputs, 4 relay (digital) outputs

EXP24-L: 24 digital inputs

Advertising
This manual is related to the following products: