Falcon user guide – RLE FMS8 User Manual

Page 62

Advertising
background image

Falcon User Guide

62

** System Menu/Help **

SS - System Status

CA - Current Alarms

KA - Kill All Alarms

LM - Log Menu

TI - Display Date/Time

AD - ADC Input Values

MS - Modem Stats

NS - Network Stats

AT - Arp Table

SC - System Confi g

DU - Dump Network Packets

NT - Network Trace

PING - Ping an IP Address

EX - Exit to Bootloader

Enter Menu Selection >

Enter Menu Selection > SC ******

** Main Confi guration Menu **

1. System Menu

2. IP Confi g Menu

3. Modem Confi g menu

4. EIA-485 Confi g menu

5. Factory Menu

6. Load/Save Confi g Data

7. Confi guration Password

8. E-Mail, SMTP Confi g Menu

X. Exit

Enter Menu Selection >

Enter Menu Selection >1

System Confi guration Menu

1. System Name: Falcon Monitoring System

2. Clock: 10/27/00 16:37:17

3. Keypad Access

4. Inputs

5. Relays

6. Battery

7. Analog Averaging: 0

8. Persistent Traps: 0

9. Slave Inputs

10. Slave Relays

11. Schedules

12. BACnet

13. Exit & Save

Enter Menu Selection >

9 - Slave Inputs
This menu provides a means to configure any slave
unit input through the configuration port of the
master unit. Slave inputs are modified one channel
at a time. After modification, the changes must be
downloaded to the slave unit in order for the changes
to take effect. The data fields and parameters
are identical to the analog/digital inputs described
earlier in this manual. The example below shows
how the slave units are accessed.

Enter Menu Selection >9

Unit2: comproom4

Unit3: NA

Unit4: NA

Unit5: NA

Slave confi guration: Enter slave

number (2-5) >2

Slave Unit: comproom4

Gathering data from unit .. done

Input Configuration Menu

Channel #A1 of 20

Current Readings: Raw = 0.000 mA Calc

= 22

1. Type: 4-20

2. Gain: 25

3. Offset: 22

4. High Limit 2: 200

5. High Limit 1: 100

6. Low Limit 1: -2147483647

7. Low Limit 2: -2147483647

8. Relay Cntrl; 1

9. Unit of Measure: Deg C

10. Label: Temp. in Room

11. Alarm Delay: 0 (Secs)

12. Hysteresis: 0

13. Alarm Dial Out: 0,0,0,0,0

14. BACnet Instance:

15. BACnet Units:

18. Email Recipients:

19. Alarm Disable Sch: None

20. Previous Channel

21. Next Channel

22. Return

DL. Download Changes to Module

Enter Menu Selection >

Advertising
This manual is related to the following products: