D900000145

Issue 3

4-6

4.8

Installation with Other Equipment

In most cases, dedicated AC mains circuits are not required for the TeamPoS
3000XL and XL

2

terminals. In rare instances, other electrical equipment sharing

power with the terminal may cause adverse effects on the terminal. When this
occurs, electrical isolation may be required and is the responsibility of the
customer or installing contractor.

Terminals at 100-240 volts

The table below details the power requirements for the TeamPoS series control
unit. Provide 100-240 volts AC, 50/60 Hz, single phase, with the following
amperage requirements:

Property

Value or Description

Grounding

The terminals are Class 1 equipment and must be
supplied via a socket-outlet which has a protective
ground contact connected to the protective ground of the
terminal.

Power system

The terminals are designed for use on a power system
with a grounded neutral, i.e., a TN or TT power system.
The terminals must not be directly connected to a power
system with impedance grounded neutral, i.e., an IT
power system.

Rated voltage and frequency

100 - 240 volts, 50/60 Hz

Rated current

1.8 A / 3.6 A

Operational freque ncy limits

47 – 63 Hz

Earth leakage current

< 1.0 mA

Power dissipation

250 watts

Maximum HRC fuse rating for
external short-circuit protection

10 A / 20 A

Main power cord:
Length
Diameter
Minimum bend radius


3.00 m (9.80 ft.)
8.0 mm (0.30 in.)
10.0 mm (0.40 in.)