Siemens S5-135U/155U User Manual

Page 112

Advertising
background image

4-46

System Manual

C79000-G8576-C199-06

If the filter mat is clogged and the power supply unit no longer receives
sufficient air, the “Alarm” LED lights up, LEDs for “Fan 1,” “Fan 2” and
“Fan 3” flash and the “Alarm” relay picks up. The fault can be cleared by
replacing the filter mat (see ordering information for the order number).

Correct the fault in the following steps:

Step

Action

1

Release the filter subdrawer.

2

Swivel the filter subdrawer downwards and pull it forwards and out.

3

Remove the old filter mat.

4

Insert a new filter mat in the filter subdrawer.

5

Place the distance grid on the new filter mat.

6

Insert the filter subdrawer in the guide rails, slide it back and swivel it up so
that it locks in place.

7

Press the Reset button.

Result:

– Fault LEDs for “Alarm,” “Fan 1,” “Fan 2” and
“Fan 3” go off.
– Contacts 11 and 12 are closed in the “Alarm” relay.

Replacing the
Filter Mat

Inadequate Air
Flow

How to Replace
the Filter Mat

Central Controllers and Expansion Units Power Supply Units