Siemens S5-135U/155U User Manual

Page 33

Advertising
background image

3-7

System Manual
C79000-G8576-C199-06

Employ special EMC measures for particular applications (see
Section 3.3.4).

S

Fit quenching elements to all inductances which are not controlled by
SIMATIC S5 modules.

S

Use incandescent bulbs for illuminating cabinets, and avoid fluorescent
lamps.

Create a standard reference potential; ground all electrical apparatus if
possible (see Sections 3.4 and 3.5).

S

Use specific grounding measures. Grounding of the control system is a
protective and functional measure.

S

System parts and cabinets with central controllers and expansion units
should be connected to the ground/protective conductor system in star
configuration. This serves to avoid the creation of ground loops.

S

In the case of potential differences between system parts and cabinets,
install equipotential bonding conductors of sufficient rating.

Installation Guidelines

Advertising