Siemens S5-135U/155U User Manual
Page 288
Advertising
6-26
System Manual
C79000-G8576-C199-06
You wish to reference modules at Slots 11, 59, 75 and 99 in the
S5-135U/155U PLC via the COR 923C, from base address 10.
Setting the base address:
Switch
Setting
Meaning
off
on
Base address:
S2.1
x
–
S2.2
x
Significance 16
S2.3
x
Significance 8
8
S2.4
x
Significance 4
S2.5
x
Significance 2
+
2
S2.6
x
Significance
1
=
10
Activating the required slots for the S5-135U/155U PLC:
Switch
Setting
Meaning
Slot No. in the
S5-135U/155U
Operable Slots
End
Address
off
on
S3.1
x
Base address + 0
11
11
10
S3.2
x
Base address + 1
27
S3.3
x
Base address + 2
43
S3.4
x
Base address + 3
59
59
13
S3.5
x
Base address + 4
75
75
14
S3.6
x
Base address + 5
83
S3.7
x
Base address + 6
91
S3.8
x
Base address + 7
99
99
17
Example of
Address Activation
Multiprocessor Operation/Coordinators