4-62

System Manual

C79000-G8576-C199-06

As of Version 6 of PSU 6ES5 955-3NA12, you can set jumper RR-LL to
choose whether the signaling relay (monitor output) should switch in the
event of battery failure as well as fan failure:

S

Jumper RR-LL open (state when delivered): relay will signal only a fan
failure

S

Jumper RR-LL closed: relay will signal a fan and battery failure.

If the backup voltage fails or a fan is at standstill, or in both cases, the
signaling relay will drop out (monitor output). The “Batt. Low” LED will
also light up.

S

Relay contacts 2-1 closed: battery backup voltage in order and fan
running

S

Relay contacts 2-3 closed: backup voltage under 2.7 V or fan failure

Note

The signaling relay in the power supply unit will drop out in the event of a
fan fault or backup battery fault. The user’s circuitry for the signaling relay
must therefore be suitable for both types of fault.

If the signaling relay drops out because of a backup battery fault and the
programmable controller is therefore switched off, the program in the main
memory may be lost. Loss of program can be avoided if an external backup
voltage (3.4 V) is present at the sockets on the front plate of the power
supply unit during shutdown of the programmable controller.

Setting the Backup
Battery Monitor

Central Controllers and Expansion Units Power Supply Units