10 technical specifications – Siemens S5-135U/155U User Manual

Page 494

Advertising
background image

9-112

System Manual

C79000-G8576-C199-06

9.7.10

Technical Specifications

6ES5 470-4UA12, 6ES5 470-4UB12 and 6ES5 470-4UC12 Analog Output
Modules

Rated output ranges
– 6ES5 470-4UA12
– 6ES5 470-4UB12
– 6ES5 470-4UC12

0 to

$10 V and 0 to 20 mA parallel for $1024 units

$10 V for $1024 units
1 to 5 V and 4 to 20 mA parallel for 0 to 1024 units

Number of outputs

8 voltage and current outputs each,
no-load and short-circuit-proof

Isolation

Yes 8 outputs with respect to M

ext

, M and L+/L–

Measured value representation

12-bit (two’s complement)

Linearity in the range of

$1024 units

$ 2 LSB = $ 0.2 %

Operational error limits (0 to 60

o

C)

$ 0.6 %

Temperature coefficient for voltage and current outputs

1 x 10

–4

/K

Permissible overrange

Approx. 25 % (

$ 1024 to $ 1272 units)

Fault current at voltage output

Approx. 25 mA

No-load voltage at current output

Approx. 18 V

Load impedance
– at voltage output
– at current output


w 3.3 kW

v 300 W

Delay between data transfer and analog value output
to > 99%

v 5ms

Capacitive load including line capacity
for -4UA12 from version 03 and
for -4UB12 and -4UC12 from version 04:

100 nF max.

1

mF max.

Permissible voltage drop on voltage output lines

$ 0.3 V at maximum output voltage

Power supply
– Digital section from system bus
– Analog section from load voltage
– Enabling for module, F+/F-


5 V

$ 5 %; approx. 250 mA

24 V; 200 to 400 mA
24 V; approx. 7 mA

Permissible potential difference between reference poten-
tial of the load and housing (U

CM

)


25 V AC / 60 V DC max.

Voltage test to VDE 0160

Between outputs and housing
tested at 500 V AC

Surge voltage test to IEC 255-4

Between outputs and L–: V

p

= 1 kV; 1,2/50

ms

Analog Input/Output Modules