Siemens S5-135U/155U User Manual

Page 401

Advertising
background image

9-19

System Manual
C79000-G8576-C199-06

9.3.9

Connecting a Compensating Box for Thermal E.M.F.

Measurement

If the room temperature fluctuations at the reference point (e.g. in the
terminal box) affect the measurement result and you do not wish to use a
thermostat, you can compensate for the effect of temperature on the reference
point with a compensating box. Between - 10 and + 70

o

C, it compensates for

the change in thermal e.m.f. cause by temperature deviation (compensating
box, see Catalog MP 11). Ensure that the compensating box has thermal
contact with the terminals.

If the compensating box is aligned at 20

o

C, this must be taken into account

in temperature evaluation (20

o

C measuring point temperature = 0 mV).

Pins 22 and 23 are extended on analog input modules as an input for the
compensating voltage. You must select a common input loop for all inputs on
mode switch 2.

The compensating box must be connected in a floating circuit. The power
supply unit of the compensating box must have a grounded shield winding to
avoid AC system interference being picked up. A separate compensating box
with its special power supply unit is required for each analog input module.

22–

A

D

Analog Input Module

MUX

M–

23+

0 V Bus

M+

+

Power
Supply
for Com-
pensat-
ing Box

Thermocouple

Terminal Box

~

=

#

Range

Card for
4 Inputs

6ES5 498-

-1AA11

Compen-
sating
Box

Figure 9-8

Connecting a Compensating Box

Analog Input/Output Modules