Siemens S5-135U/155U User Manual

Page 455

Advertising
background image

9-73

System Manual
C79000-G8576-C199-06

Measuring point-related error signal
– for overflow
– for broken wire

Yes
Yes, configurable
(at

$ 50 mV, $ 500 mV and Pt 100)

Max. permissible input voltage without destruction

$18 V; 75 V for 1 ms max. and duty ratio 1:20

Interference suppression for f = n x (50/60 Hz

$1 %)

– with common-mode interference
– with differential-mode interference

w 86 dB, but $1 V max.

w 40 dB, noise voltage amplitude
but 100 % max. of measuring range
referred to peak value

Error referred to rated value
– linearity
– tolerance
– polarity reversal error
– temperature error

$ 1 unit

$ 1 unit

$ 1 unit
1 x 10

–4

/K

Error caused by cards with input range

$ 1 V/$ 5 V /$ 10 V

$ 20 mA/4 to 20 mA

2 x 10

–3

; TC =

$ 10 x 10

–5

/K

10

–3

; TC =

$ 5 x 10

–5

/K

You select the desired mode of the analog input module by setting mode
switches I and II according to the following table.

Note that all the rockers of both mode switches marked with a dot must be
set, and some functions are defined by several rockers (e.g. 8- to 16-channel
operation, broken wire signal for 8 or 16 channels).

To activate the desired modes, press the rockers down on the side marked
with a dot.

Setting the Mode

Analog Input/Output Modules

Advertising