12 broken wire signal – Siemens S5-135U/155U User Manual

Page 404

Advertising
background image

9-22

System Manual

C79000-G8576-C199-06

9.3.12

Broken Wire Signal

An open-circuit in the lines to a resistance thermometer is indicated as
follows:

Broken Wire at

Module Reaction, Encoded Value

Error Bit E

M+
M–

Pt 100

I

C+

I

C–

0
0

0

1)

0
0

1
1
1
0
0

1)

With the 460 analog input module, the value 0 is also encoded for the intact Pt 100 resistances

because the auxiliary circuit is interrupted; the error bit will not be set for these channels.

If the mode “without broken wire signal” is selected on the module, an
open-circuit of the resistance thermometer is indicated with an overflow.

Unassigned channels can be used for voltage or current measurement.

If a line of the auxiliary circuit (I

C+

, I

C-

) is interrupted, the “negative range

limit” is encoded for all inputs and the overflow bit is set to “1.” In the event
of a sensor or measuring line open-circuit, the error bit is additionally set to
“1” for the relevant channel.

Broken Wire
Signal in the
Standard Pt 100
Range

Broken Wire
Signal in the
Extended Pt 100
Range