You set a base address from 1 to 31 with DIL switch S2. You can reference
the modules selected by the multiplexer under this address and the following
seven addresses. The base address results from the sum of binary
significances activated by the On setting of the switch.

Factory setting:

Switch

Setting

Meaning

off

on

’0’

’1’

S2.1

x

S2.2

x

Significance 16

S2.3

x

Significance 8

S2.4

x

Significance 4

S2.5

x

Significance 2

S2.6

x

Significance

1

(base address = 1)

You use switch S3 to activate the numbers and slots to be reached via the
COR 923C.

Factory setting:

Switch

Setting

Meaning

Slot No. in the
S5 135U/155U

off

on

S5-135U/155U

S3.1

x

Base address + 0

11

S3.2

x

Base address + 1

27

S3.3

x

Base address + 2

43

S3.4

x

Base address + 3

59

S3.5

x

Base address + 4

75

S3.6

x

Base address + 5

83

S3.7

x

Base address + 6

91

S3.8

x

Base address + 7

99

An example for setting the PG multiplexer is given on the following page.