Siemens S5-135U/155U User Manual

Page 289

Advertising
background image

6-27

System Manual
C79000-G8576-C199-06

All the output signals required for coordination (arbitration) can be
interrupted by removing a jumper plug. This is necessary to operate the COR
923C as a PG multiplexer in the EU S5-185U.

Coordination Section

in operation

out of operation

All jumpers of EP 61 closed

All jumpers of EP 61 open

1

8

EP 61

9

16

When the unit is delivered, all jumpers are closed.

The fault register is an 8-bit register and is readable by the CPU under
address FEFFH. The register is written to by the bus monitor in the event of a
bus error. Each CPU is assigned one bit of the fault register which is set to 1
in the event of an error. The register is cleared each time the Stop signal
becomes inactive.

Fault register FEFFH

Bit = 1: Bus error from CPU 1

Bit = 2: Bus error from CPU 2

Bit = 3: Bus error from CPU 3

Bit = 4: Bus error from CPU 4

7

4

3

2

1

0

Not assigned

The fault register can be read by all CPUs, allowing central functions to be
initiated.

Note

The fault register and the page register are at address FEFFH (FFEFFH with
the CPU 948). The page register is addressed by writing to FEFFH, and the
fault register is addressed by reading out FEFFH.

Jumpers to
Switch off the
Coordination
Signals

Fault Register

Multiprocessor Operation/Coordinators

Advertising