Siemens S5-135U/155U User Manual

Page 121

Advertising
background image

4-55

System Manual
C79000-G8576-C199-06

6ES5 955-3NF42

6ES5 955-3NC42

Protection and monitoring

Voltage Monitor

Monitors voltage for
<14 V and >16 V

Monitors voltage for
<14 V and >16 V

Overvoltage shutdown V

o/p1

6 V

$ 5%

6 V

$ 5%

Undervoltage signal V

o/p1

4.75 V + 3%

4.75 V + 3%

Current limiting for overload

1.0 to 1.2 I

o/pN1

1.0 to 1.2 I

o/pN1

Test sockets for Io/p

1

on front plate

(3 V

¢ 18 A)

linearity range 0.5 V/2.8 A
to 3 V/18 A

(3 V

¢ 40 A)

linearity range 0.5 V/6.6 A
to 3 V/40 A

Signaling section

Signals for SIMATIC S5,
relays “Fan Warning, Fan Alarm,
Warning” 250 V/3 A

Signals for SIMATIC S5,
relays “Fan Warning, Fan Alarm,
Warning” 250 V/3 A

Green LED: “5V o.k.” for V

o/p1

LED lights up if
4.75 V < V

o/p1

LED lights up if
4.75 V < V

o/p1

Output 2

Rated output voltage V

o/pN2

DC 24 V (+ 25%, -12.5%)

DC 24 V (+ 25%, -12.5%)

Rated output current I

o/pN2

1 A

2.8 A

Total current X2 and front terminals

1 A max.

2.8 A max.

Ripple

v 1% of V

o/p2

v 1% of V

o/p2

Spikes

v 2% of V

o/p2

v 2% of V

o/p2

Protection and monitoring

Current limiting for overload

1 to 1.3 I

o/pN2

1 to 1.3 I

o/pN2

Green LED: “24V o.k.” for V

o/p2

LED lights up if
V

o/p2

> 19.9 V to 21.1 V

LED lights up if
V

o/p2

> 19.9 V to 21.1 V

Maximum permitted capacity

0.2 mF

0.8 mF

Output 3

Rated output voltage V

o/pN3

DC 15 V (

$ 5%)

DC 15 V (

$ 5%)

Rated output current I

o/pN3

0.5 A

2 A

Ripple

v 1% of V

o/p3

v 1% of V

o/p3

Spikes

v 3% of V

o/p2

v 3% of V

o/p2

Maximum permitted capacity

100 mF

750 mF

Protection and monitoring

Overvoltage shutdown V

o/p1

17 V

$ 5%

17 V

$ 5%

Current limiting for overload

1 to 1.5 I

AN3

During startup 4

I

AN3

for 40 ms

1 to 1.5 I

AN3

Green LED: “15V o.k.” for V

o/p3

LED lights up if 14.2 to 14.7 V <
V

o/p3

< 16.1 to 17.9 V

LED lights up if 14.2 to 14.7 V <
V

o/p3

< 16.1 to 17.9 V

Maximum permitted capacity

10 mF

10 mF

Central Controllers and Expansion Units Power Supply Units