Noise immunity, electromagnetic compatibility (EMC)

RFI suppression

Limit value class

To EN 55011
A

2)

Conducted interference on AC supply lines (230 V AC)

to EN 61000-4-4 / IEC 1000-4-4 (burst)
to IEC 1000-4-5

between two lines (

ms pulses)

between line and ground (

ms pulses)

2 kV

1 kV
2 kV

DC supply lines (24 V supply) to EN 61000-4-4 / IEC 1000-4-4
(burst)

2 kV

Signal lines to EN 61000-4-4 / IEC 1000-4-4 (burst)

2 kV

1)

Immunity to discharge of static electricity to EN 61000-4-2 /
IEC 1000-4-2 (ESD)

2)

Immunity of 4 kV contact discharge
(8 kV air discharge) is ensured with proper
installation (see Chapter 3).

Immunity to electromagnetic RF field

2)

amplitude modulated to ENV 50140 / IEC 1004-4-3

80 to 1000 MHz
10 V/m
80% AM (1 kHz)

Immunity to electromagnetic RF field

2)

pulse-modulated to ENV 50204

900 MHz
10 V/m
50% ED

Immunity to high-frequency sinusoidal to ENV 50141

0.15 to 80 MHz
10 V
80% AM

Mechanical data

Mechanical requirements

Installation in stationary equipment, subject to
vibration; installation on ships and in vehicles if
special installation rules are observed, but not on
the engine.

Weight

approx. 14 kg

Dimensions (W x H x D)

482.6 x 432 x 310 mm

1)

Signal lines which do not serve to control the process, for example connections to the external I/O etc.: 1 kV

2)

When cabinet door is closed.

Central Controllers and Expansion Units Power Supply Units