Siemens S5-135U/155U User Manual

Page 144

Advertising
background image

5-4

System Manual

C79000-G8576-C199-06

Note

All other jumpers on the CPU 948B -3UA13 or the CPU 948B -3UA23 are
required for quality testing by the manufacturer. You must not change these
jumper settings.

!

Caution

Switch off the power supply before removing or inserting the module.

Proceed as follows to insert the CPU in the central controller:

Step

Action

1

Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.

2

Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U CC from slot 11.

3

Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.

4

Press the locking pin inwards on the bottom of the module and
rotate it 90

_ clockwise.

5

Secure the upper locking bar.

Note

If you install the CPU 948 -3UA13 or the CPU 948 -3UA23 as the
replacement for a double-width CPU 948, you must cover the slot which has
been freed up with a blanking plate.

Removing and
Inserting the
Module

Insertion

CPUs, Memory Cards, Memory Submodules, Interface Submodules