Siemens S5-135U/155U User Manual

Page 403

Advertising
background image

9-21

System Manual
C79000-G8576-C199-06

9.3.11

Connecting Resistance Thermometers in the Extended Pt 100

Range

The series-connected resistance thermometers (up to 8 Pt 100s) are fed with a
current of 2.5 mA (I

C+

/I

C-

) by a constant current generator. The voltage at the

Pt 100s is picked off at measurement inputs M+ and M-.

In this mode, the temperature range of approximately -100

°

C to +100

°

C has

a more accurate resolution. The mode is printed on the cover of the module
as follows: “resistance thermometer compensated low range.”You should
only use the 6ES5 498-1AA11 range card (

" 50 mV / 500 mV).

Unused inputs must be connected in parallel to a wired input. In the
following figure, for example, these are the inputs CH4 to CH7.

M+

M–

Ch0

M+

M–

Ch1

M+

M–

Ch2

M+

M–

Ch3

M+

M–

Ch4

M+

M–

Ch5

M+

M–

Ch6

M+

M–

Ch7

Ic–

Ic+

L+

L–

6ES5498-
1AA11

6ES5498-
1AA11

24V

M24V

2.5mA

Figure 9-10

Connecting Resistance Thermometers in the Extended Pt 100 Range

Analog Input/Output Modules