Siemens S5-135U/155U User Manual

Page 217

Advertising
background image

5-77

System Manual
C79000-G8576-C199-06

QVZ LED

on

During direct access or process image update, a module
addressed by the program no longer acknowledges although

S

either it has acknowledged in single processor operation
upon reset of the CPU 922 in the area of the process
image (IB 0 to 127, QB 0 to 127) and has been entered as
present in the “9th track” (see Programming Guide,
CPU 922),

it h

b

t

d i DB 1 ( dd

li t) i

S

or it has been entered in DB 1 (address list) in
multiprocessor or single-processor operation and has been
recognized as present during the reset.

Possible causes

S

Module failure.

S

Module was pulled out during operation, in the stop state
or in the Off state without a subsequent reset.

ADF LED

on

The user program has referenced an I/O address under which
no module is inserted.

ZYK LED

on

The maximum cycle time has been exceeded.

BASP LED

on

Command output is inhibited and the digital outputs will be
directly switched to the safe state.

A detailed description of interrupt and error handling can be found in the
CPU 922 Programming Guide.

LEDs for Fault
Indication and
Signaling

CPUs, Memory Cards, Memory Submodules, Interface Submodules