LEDs SI1 and SI2 indicate faults in communication via interfaces SI1
and SI2:

LED SI1

LED SI2

Cause

on

on

Communication is not possible at both interfaces.
Internal fault.

on

off

SI1:
No communication possible.
Internal fault.

SI2:
Interface is initialized and ready.
LED SI2 is always off if no interface module is
inserted.

off

on

SI1:
Interface is initialized and ready.

SI2:
No communication possible. Wrong module
inserted or internal fault.

off

off

Both interfaces are initialized and ready.

LED SI2 is always off if no interface module is
inserted.