4-21

System Manual
C79000-G8576-C199-06

Based on the example of the 6ES5 955-3LF41 power supply unit, the
following figure shows the arrangement of inputs and outputs on the front
plate of the power supply units:

6ES5955-3LF42

L1

N

1

2

3

4

5

6

7

8

9 10

11

14

12

15

13

16

17 18

+

+

+

+

AC120V4,5A
AC230V2,6A

CAUTION!
Disconnect
before
removing
power supply!

Voltage
selector

Unlock
Fan 1

Unlock
Fan2

Unlock

Fan3/Res.Batt

.

Input
DC 24V Ext.

AC line 50/60 Hz

Enable
Power supply

Voltage Monitor

Fan

Battery

Ext.Batt.
DC 4,5V

Fault

Warning

Alarm

Warning
max. AC 250V/3A

max. AC 250 V/ 3A

V

o

ltage low

Fan1

MB low

Fan2

RB low

5V

o.k.

Fan3

Reset

Alarm

EN UH

Power

I

I

1

234

5

6

7

8

9

10

Batt. 3,6V/5Ah

Replace by
trained personnel
only!

Use battery holder

C98100-A1155-B21
only!

SIEMENS

Output

DC 24V 2,8A

DC 5/15/24V

Internal

3V=40A

15V

o.k.

24V

o.k.

Batt.+Fan

The following table provides an overview of the labelling and purpose of the
inputs and outputs:

ID

Label

Element

Purpose

A

AC 120V 4.5A
AC 230V 2.6A

Screw terminals
1, 2, 3

AC connection and protective conductor

B

EN

Screw terminal 4

Enable Power Supply
Control input for power supply

C

U

H

Screw terminal 5

Supply for EN

D

Input
DC 24V Ext.

Screw terminals
6 and 7

Voltage Monitor
Monitors 24 V load voltage for > 16 V

E

Fan Warning
max. 250V/3A

Screw terminals
8, 9, 10 (relay)

Indicates failure of a fan

F

Fan Alarm
max. 250V/3A

Screw terminals
11, 12, 13
(relay)

Indicates failure of at least two fans and
inadequate air flow; if jumper set
accordingly, output enable is the second
signal source

G

Battery
Warning
max. 250V/3A

Screw terminals
14, 15, 16
(relay)

Indicates that lithium battery or
rechargeable battery has dropped below
limit

H

3V = 40A

2 test sockets

Current measurement sockets for test
purposes only; no continuous operation;
linearity range 0.5 V/6.6 A to 3 V/40 A

I

Output
DC 24V 2.8A

Screw terminals
17, 18

Enable voltage for I/O modules

J

Ext.Batt.
DC 4.5V

2 input sockets

Input for an external 4.5 V backup
voltage

Inputs and
Outputs

Central Controllers and Expansion Units Power Supply Units