Siemens S5-135U/155U User Manual

Page 62

Advertising
background image

3-36

System Manual

C79000-G8576-C199-06

Where subracks (CC and EU) are arranged one above the other, the
installation clearances in the following table must be observed.

Upper Subrack

Lower Subrack

Min. Clearances

Max. Clearances

S5-135U/ 155U
or
S5-115U

S5-135U

75 mm

87 mm if baffle

is used

The maximum clearance
is limited by the lengths
of connecting cables for

h i

f

d l

or
S5-90U/ 95U/ 100U

S5-115U with fan

60 mm

g

the interface modules.

S5-90U/ 95U/ 100U

S5-115U without fan

100 mm

S5-90U/ 95U/ 100U

75 mm

The following two points should be observed to improve the air circulation
within the cabinet:

S

The expansion unit with the greatest power dissipation to be removed
should be the upper unit.

S

If subracks of the S5-135U/155U series are installed together with
subracks of the S5-90U to 115U series in one cabinet, the rear panels of
all subracks must be at the same distance from the rear wall of the
cabinet.

Installation Guidelines