Siemens S5-135U/155U User Manual

Page 113

Advertising
background image

4-47

System Manual
C79000-G8576-C199-06

If it should be necessary to replace the power supply unit in a system during
commissioning or during operation, we recommend you proceed as follows:

Requirement:
Redundant backup, “Spare power supply” without rechargeable battery
(standard spare part).
The lithium battery in the rack is in full working order.

Step

Action

1

Disconnect the faulty power supply from the system voltage and remove it.

2

Set the jumpers on the spare power supply according to your needs.

3

Push the spare power supply into the rack and screw it in place.

4

Remove the right-hand fan subassembly from the defective power supply.

5

Remove the rechargeable battery from the fan sub- assembly.

6

Replace the right-hand fan subassembly in the defective power supply.

7

Remove the right-hand fan subassembly from the spare power supply.

8

Connect up the spare power supply.

9

Switch on the system voltage and the power supply in any order.

Reaction:
– The system runs up
– Both fans run at an increased speed
– The LEDs “Fan 3” and “RB low” light up.

10

Insert the rechargeable battery in the fan subassembly and connect it up.

11

Reinsert the right-hand fan subassembly.

12

After the system has run up, press the reset switch on the spare power
supply.

Reaction:
– The LED “Fan 3” goes out
– The fans run at their normal speed again
– The LED “RB low” shows the charge state of the rechargeable battery.

Replacing a Power
Supply Unit

Central Controllers and Expansion Units Power Supply Units

Advertising