Siemens S5-135U/155U User Manual

Page 135

Advertising
background image

4-69

System Manual
C79000-G8576-C199-06

Output 2 (bus)

Rated output voltage V

o/p2

24 V DC +25% / -20%

Rated output current I

o/p2

0.8 A

Total current rating
24V-/ 15V output

v 0.8 A

Ripple

Input voltage ripple

Protection and monitoring

Fuse for overcurrent protection
Test sockets for V

o/p2

– green LED 15V/24V o.k. for V

o/p2

(fuse monitor)

1.5 A fast; 250 V; 6.3 x 32 mm
on front plate (24 V test)
The LED lights up when V

o/p2

> 17.9 to 18.5 V

Output 2 (front)

Rated output voltage V

o/pN4

24 V DC +25% / -24%

Rated output current I

o/pN4

0.4 A

– Capacitive load

< 100 nF

Protection and monitoring

Overcurrent protection by current limiting I

o/p4

Test sockets for V

o/p2

– green LED 24V o.k. for V

o/p4

> 0.44 A
on front plate (24 V test)
The LED lights up when V

o/p4

> 16 V

$ 20%

Total current rating of 24 V voltages (bus and front)

must not exceed 0.8 A

Output 3 with 15 V auxiliary submodule

Rated output voltage V

o/pN3

15 V DC

$ 5%

Rated output current I

o/pN3

0.5 A

Ripple

v 5% of V

o/pN3

Protection and monitoring

Overvoltage protection (output is short-circuited
at V

o/p3

)

Undervoltage signal (LED 15V/24V o.k.
on front plate goes off at)
Overcurrent protection I

o/p3

by current limiting

Test socket for V

o/p3

w 18.5 V

v 14 V $ 3%
> 0.5 to 1.5 A

on front plate (15 V test)

Fans

Fan type

2 axial fans

Input voltage

24 V DC

Flow rate per fan

160 m3/h (no-load value)

Fan monitoring

Air flow monitoring with PTC thermistors as sensors;
stoppage of one or both fans is detected and signaled to the
exterior via Fan Fault LED and relay contacts, and results
in shutdown of output voltage (switched off via jumper
F-R).

Expected service life of a fan

30 000 to 40 000 h typical at 55

o

C;

40 000 to 50 000 h typical at 30

o

C;

Isolation primary/sekondary
and test voltages

No

Weight

3.75 kg

Environmental data

See technical specifications of the S5-135U/155U CC

RFI suppression

DIN VDE 0871, A

Central Controllers and Expansion Units Power Supply Units

Advertising