Siemens S5-135U/155U User Manual

Page 36

Advertising
background image

3-10

System Manual

C79000-G8576-C199-06

À

Grounding strips

If there are no large-area metal-to-metal connections, you must
connect inactive metal parts such as cabinet doors and supports
with grounding strips. These should be short and have a large surface.

Á

Cabinet members

The cabinet members should have a large-area connection to the
cabinet housing (metal-to-metal connection).

Â

Mounting bracket for subrack

There must be a large-area metal-to-metal connection between
cabinet member and mounting bracket.

Ã

Signal lines

With shielded signal lines, the shield must be secured to the

protective conductor bar or an additionally fitted shield bar using
large-area cable clamps.

Ä

Cable clamp

The cable clamp must enclose and make contact with the shield braid
over a large area.

Å

Shield bar

This bar must have a large-area connection to the cabinet members
(metal-to-metal connection). It serves for grounding the cable shields.

Æ

Protective conductor bar

The protective conductor bar must have a large-area connection to
the cabinet members (metal-to-metal connection). The protective
conductor bar must be connected to the protective conductor system
via an external conductor (at least 10 mm

2

). This is essential for

providing a reliable path to ground for fault currents and interference
currents.

Ç

Conductor to the protective conductor system (ground point)

The conductor must have a large-area connection to the protective
conductor system (ground point).

Installation Guidelines

Advertising