Please observe the following points when connecting the shield:

S

Use metal cable clamps for securing the braided shield. The clamps must
enclose the shield over a large area and provide a good contact.

S

Connect the shield to a shield bar immediately after the cable entry into
the cabinet. Route the shield as far as the module but do not connect it
there again.

О

О

О

О

О

О

О

ОО

ОО

ОО

О

О

О

ОО

О

О

О

ОО

О

О

О О

Figure 3-5

Example of Securing Shielded Lines with Cable Clamps

Installation Guidelines