Broken Wire Signal for Resistance Thermometers

An open-circuit in the lines to a resistance thermometer is indicated as
follows:

Broken Wire at

Module Reaction, Encoded Value

Error Bit E

M+
M–

Pt 100

I

C+

I

C–

0
0

0

0
0

1
1
1
1
1

If the mode “without broken wire signal” is selected on the module, an
open-circuit of the resistance thermometer is indicated with an overflow.

Unassigned channels can be used for voltage or current measurement if the
current flow outputs relating to the particular measuring channel are shorted
with a wire jumper. Without this jumper, the error bit would be set for this
channel and the value 0 would be encoded.

When set to “resistance thermometer,” switch 7 of mode switch I of the 465
analog input module allows broken wire monitoring of the I

C+

lines to the

resistance thermometer (Pt 100 constant current supply). In the event of
open-circuit of this line, the error bit is set as for the other lines.

At the “voltage/current” (mV/mA) setting, the I

C+

lines are not monitored for

broken wire. (The error bit is not set for an open-circuit of this line.) You
should choose this switch setting if you exclusively measure voltages or
currents.

Broken Wire
Monitoring

Analog Input/Output Modules