A power socket should be fitted in each cabinet for the AC supply to
programmers. The sockets should be powered from the distribution system to
which the protective conductor for the cabinet is also connected.

Use incandescent bulbs, such as LINESTRA lamps, for cabinet lighting.
Avoid using fluorescent lamps because they generate interference fields. If
the use of fluorescent lamps cannot be avoided, apply the measures shown in
the following figure.

Shielded Cable

Screen Over the Lamp

Metal-Enclosed Switch

AC Filter or
Shielded Power Cable

Figure 3-7

Measures for Interference Suppression of Fluorescent Lamps in a
Cabinet

AC Power
Connection for
Programmers

Cabinet Lighting