Siemens S5-135U/155U User Manual

Page 119

Advertising
background image

4-53

System Manual
C79000-G8576-C199-06

6ES5 955-3LF42

6ES5 955-3LC42

Output 3

Rated output voltage V

o/pN3

15 V DC (

$ 5%)

15 V DC (

$ 5%)

Rated output current I

o/pN3

0.5 A

2 A

Ripple

v 1% of V

o/p3

v 1% of V

o/p3

Spikes

v 3% of V

o/p2

v 3% of V

o/p2

Protection and monitoring

Overvoltage shutdown V

o/p3

17 V

$ 5%

17 V

$ 5%

Current limiting for overload

1 to 1.5 I

o/pN3

During startup 4

I

AN3

for 40 ms

1 to 1.5 I

o/pN3

Green LED “15V o.k.” for V

o/p3

LED lights up if
14.2 to 14.7 V < U

A3

< 16.1 to

17.9 V

LED lights up if 14.2 to 14.7 V <
U

A3

< 16.1 to 17.9 V

Maximum permitted capacity

10 mF

10 mF

Backup battery

Type
Capacity
No-load voltage
Voltage under load
Storage life
Service life in operation
(see Section 4.3.4 for backup times)

Lithium thionyl chloride
5 Ah
3.6 V
3.4 V
approx. 10 years
3 years max.

Rechargeable battery

Type
Capacity
Rated voltage
Service life in operation
(see Section 4.3.4 for backup times)
Protection against exhaustive discharge

Nickel cadmium
1.2 Ah
3.6 V
6 years at 40

°

C (104

°

F)

yes

Service life of fans

approx. 50.000 h at 40

°

C

approx. 50.000 h at 40

°

C

Weight

approx. 5.8 kg

approx. 5.8 kg

Noise emission

58 dBA

58 dBA

Environmental data

See technical specifications of the S5-135U/155U CC

Central Controllers and Expansion Units Power Supply Units