5 6es5 434-4ua12 digital input module – Siemens S5-135U/155U User Manual

Page 351

Advertising
background image

8-39

System Manual
C79000-G8576-C199-06

8.4.5

6ES5 434-4UA12 Digital Input Module

Rated input voltage (LH+)

DC 5 to 15 V

Rated input voltage (L+)

DC 12 to 24 V (NAMUR)

1)

Number of inputs

32

Isolation

Yes, 1 group of 32 inputs

Input voltage TTL:

for logic 0

for logic 1

CMOS:

for logic 0
for logic 1

0 to 0.8 V
2.4 to 5.0 V
0 V to 0.3 x LH+
0.7 V x LH+ to 1 x LH+

Rated input current

TTL:

for logic 0
for logic 1

CMOS:

for logic 0
for logic 1

NAMUR:

for logic 0
for logic 1

–1 mA
0.1 mA or open input
–1 to –3 mA (5 to 15 V)
0.1 to 0.3 mA (5 to 15 V)
v 1.2 mA

w 2.1 mA

Internal resistance

1 kilohm typical

Line resistance

50 ohms max.

Input frequency

100 Hz max.

Delay time

for positive-going edge
for negative-going edge


3 ms typical (1.4 to 5 ms)
3 ms typical (1.4 to 5 ms)

Coincidence factor (total load capability)

100 %

Permissible line length

TTL/CMOS
NAMUR

200 m max. unshielded
600 m max. unshielded

Power supply

Digital section from system bus

5 V, 80 mA typical

Supply voltage L+/L–

24 V (20 to 30 V)

Current consumption at L+/L–

100 mA each

Current consumption at LH+/LH–

150 mA each at 15 V input voltage

Current output from LH+/LH–

120 mA each at 8.5 V sensor supply (NAMUR)

2)

Power dissipation (rated operation)

5.5 W

Enable input (F+/F–)

Rated input voltage

5/ 15/ 24 V DC

Input voltage

for logic 0
for logic 1

–15 to 2 V
4 to 33 V

Rated input current

5 mA

Permissible line length

100 m max.

Voltage test to VDE 0160

Between group and ground point: 1250 V AC

Mechanical specifications

Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.45 kg

1)

NAMUR = Sensor with current output to DIN 19234, Standards Committee for Measurement and Control.
However, the module is not intrinsically safe.

2)

The current consumption from L+/L- increases accordingly.

Digital Input/Output Modules