Siemens S5-135U/155U User Manual

Page 139

Advertising
background image

4-73

System Manual
C79000-G8576-C199-06

The following applies to selecting the cables for the terminals:

Terminals

Cabling

Max. Permissible Cable

Cross-Sections

Power supply AC line

Phase

L 1

4 mm

2

solid or 2.5 mm

2

flexible

Neutral

N

4 mm

2

solid or 2.5 mm

2

flexible

Protective conductor

4 mm

2

solid or 2.5 mm

2

flexible

Relay terminals, also suitable
to 230 V AC / 3 A

4 mm

2

solid or 2.5 mm

2

flexible

For installing and removing the fan submodule, refer to the instructions in
Section 4.3.2 on the power supply unit. These also apply in principle here.

FFor wiring up the fan submodule, refer to the instructions in Section 4.3.2
on the power supply unit. These also apply in principle here.

The fan submodule is switched on when the line voltage for the central
controller or expansion unit is switched on.

!

Caution

If you have set the voltage selector switch on the -3LA11 to 120 V, but the
actual voltage value is 230 V, the fan submodule may be damaged when line
voltage is switched on.

Fan submodule faults are indicated via relay contacts (“Monitor Output”) and
an LED.

The following table shows when the relay contacts are open or closed:

Fan Submodule

Relay Contact 1-2

Relay contact 2-3

Switched off

open

closed

In normal operation

closed

open

During fault

open

closed

In the case of a fault, the red LED “Fan Fault” lights up.

Selecting Cables

Installing and
Removing the Fan
Submodule

Wiring up the Fan
Submodule

Switching on the
Fan Submodule
for the First Time

Fault Indications/
Fault Diagnostics

Central Controllers and Expansion Units Power Supply Units