16 6es5 457-4ua12 digital output module – Siemens S5-135U/155U User Manual

Page 374

Advertising
background image

8-62

System Manual

C79000-G8576-C199-06

8.4.16

6ES5 457-4UA12 Digital Output Module

Rated supply voltage L+

24 to 60 V DC

Number of outputs (decoupled via diodes)

16, short-circuit protected

1)

Isolation

Yes, 16 outputs

Range for supply voltage

20 to 72 V DC

Fusing

16 x 1 A, slow

Output voltage

for logic 1:

(L+)-Switch

(L–)-Switch

for logic 0:

(L+)-Switch

(L–)-Switch

L+ – 2.5 V min.
2.5 V max.
3 V max.
L+ – 3 V min.

Switching current (resistive, inductive load)

5 mA to 0.5 A

2)

Residual current at logic 0

1 mA max.

Switching current for lamps

0.22 A max. (5 W)

Switching frequency

with resistive load
with inductive load

100 Hz max.
2 Hz max. at 0.5 A

Breaking voltage (inductive)

Limited to L+ – 75 V

3)

Coincidence factor (total load capability)

ventilated
not ventilated


100 %
50 %; 100 % up to 35

o

C

Permissible line length

400 m max. unshielded

Power supply

Digital section from system bus

5 V, 120 mA typical

Power dissipation (rated operation)

13.0 W

Enable input (F+/F–)

Rated input voltage

24 to 60 V DC

Input voltage

for logic 1
for logic 0

13 to 72 V
– 72 to 8 V

Rated input current

at 24 V DC
at 48 V DC
at 60 V DC

2.5 mA
5 mA
6.5 mA

Permissible line length

200 m max.

Short-circuit monitoring

Indicator for signaling output (H+, H–)

Red LED for 16 outputs

Output voltage as L+ switch

for logic 1
for logic 0


L+ – 5 V min.
3 V max.

Switching current

10 mA max., short-circuit protected

Voltage test to VDE 0160

Between two groups: 1250 V AC;
Between group and ground point: 1250 V AC

Mechanical specifications

Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.6 kg

1)

Short-circuit protection responds with line resistance 9 ohms at 24 V DC, 30 ohms at 60 V DC.

2)

One digital input is permissible as minimum load.

3)

At L+ voltages of more than 72 V, the logic 0 of the output can rise to 13 V. A digital input follower will interpret this signal
as a logic 1 (possible fault).

Digital Input/Output Modules