Siemens S5-135U/155U User Manual

Page 198

Advertising
background image

5-58

System Manual

C79000-G8576-C199-06

The mode switch has two settings:

In the RUN setting, the CPU 928-3UA21 processes the user program when
the green RUN LED is lit.

The CPU 928-3UA21 goes to the stop state when you switch from RUN to
STOP. The red STOP LED then lights up.

You can initiate the Overall Reset, Reset and Restart functions with the
momentary-contact mode switch:

Momentary-contact switch down
With an overall reset, all RAM areas are erased and initialized.

Momentary-contact switch up
During a reset, all flags, timers, counters and the process image will be
erased. OB 20 will be invoked. Processing of the user program will start from
the beginning again.

Momentary-contact switch at midpoint
With a restart, processing of the user program will continue from the point of
interruption. The statuses of flags, timers, counters and the process image are
retained during stoppage of the CPU.

RUN

LED

STOP

LED

Status

on

off

The CPU is in the RUN state.

off

on

The CPU is in the STOP state. After a stop
request by switch or PG function, the STOP LED
is continuously lit because the transition to the
STOP state was requested by the user or, in
multiprocessor operation, by another CPU, and
was not caused by the CPU itself.

off

off

The CPU is in the INITIAL START or program
check state.

off

slow

flashing

The CPU is in the STOP state. The CPU has
caused a transition to the STOP state (possibly
also for the other CPUs). If you set the mode
switch to STOP, the flashing LED becomes
continuously lit.

off

rapid

flashing

The CPU is in the STOP state. An overall reset
has been requested. This request can be initiated
by the CPU itself or by operator action.

Mode Switch

RUN

STOP

Momentary-
Contact Mode
Switch

OVERALL RESET

RESET

Restart

Status Indicators

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Advertising